Errata
NFPA 70®
National Electrical Code®
2017 Edition
Reference: 300.4, Informational Note, and Table 310.104(A)
Errata No: 70-17-1
Code-Making Panel 3, Code-Making Panel 6, and the Correlating Committee on National Electrical Code
note the following errors in the 2017 edition of NFPA 70®, National Electrical Code®.
1. Delete the Informational Note to 300.4:
Infonnational Note: Minor damage to a raceway, cable armor, or cable insulation does not necessarily
violate the integrity of either the contained conductors or the conductors’ insulation.
2. In Table 310.104(A), Moisture-resistant thermoplastic, add a missing “0” (zero) to the first entry in the
“mils” column to read as follows:
Table 310.104(A) Continued
Thickness of Insulation
Trade Name
Type
Letter
Maximum
Operating
Temperature
Application
Provisions
Insulation
AWG or
kcmil
mm
mils
Outer Covering2
Moisture-
TW
60° C
Dry and wet locations
F lame-retardant,
14-10
0.76
30
None
resistant
(140° F)
moisture-
8
1.14
45
thermoplastic
resistant
6-2
1.52
60
thermoplastic
1-4/0
2.03
80
213-500
2.41
95
501-1000
2.79
110
1001-
3.18
125
2000
Issue Date: September 29, 2016
(Note: Electronic products and pamphlet reprints may have this errata incorporated. For current
information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/docinfoI
Copyright © 2016 All Rights Reserved
NATIONAL FIRE PROTECTION ASSOCIATION